[vc_row][vc_column width=”3/4″][mk_icon_box icon=”mk-icon-file-pdf-o” text_size=”17″ font_weight=”inherit” style=”simple_ultimate” icon_size=”small” rounded_circle=”false” icon_location=”left” circled=”false” icon_color=”#dd3333″ icon_circle_color=”#f97352″ box_blur=”false” margin=”30″ title_color=”#000000″]Datasheet .pdf[/mk_icon_box][vc_column_text disable_pattern=”true” align=”left” margin_bottom=”0″]
Description
The Model N-Pipe Type 2V system for biomass storages integrates VID Fire-Kill low pressure watermist nozzles type BM-1 with thin walled stainless steel pipes. One N-Pipe Type 2V is 6 meters and it includes 12 nozzles. The system is designed for use in different applications, for example in large indoor biomass storage and power plants.The design saves cost on fittings as well as reduces the risk of getting impurities into the systems when nozzles are installed since there are less connections. The design also ensures correct nozzle spacing installation. The system is to be installed in rows covering the entire enclosure either in designated zones or connected into one large zone.
Approval
The Model N-Pipe Type 2V system for biomass storages has successfully been fire- and component tested to DFL test method 90329-3 with amendments 150225-2, designed in accordance with CEN/TS 1492 annex B.
Application areas
The Model N-Pipe Type 2V system for biomass storages is designed to protect dry or wet feedstock material typically in sized less than 150 mm in any dimensions and stored in piles up to a height of 8 m.
N-Pipe Type 2V summary:
- Robust design, reducing the need of fittings
- Small nozzle pitch allows the water to distribute very fine and even
- Large nozzle orifices reducing possibility of clogging
- Low water pressure
- Low water flow
Technical Specifications
[mk_table style=”style3]
Summary | |
Min. water pressure | 4 bar |
Max. water pressure | 16 bar |
K-value per N-pipe Type 2V –pipe (6m) | 33.6 (l/min/√bar) |
K-value per nozzle | 2.8 (l/min/√bar) |
Nominal min. under pressure | 67.2 l/min |
Drop size | DV90 < 300µm |
[/mk_table]
[mk_table style=”style3]
Application areas | |
Nozzle pitch N-pipe Type 2V -pipe | 1 m |
N-pipe Type 2V –pipe adjacent spacing | 3 m |
Min. height biomass pile | 4 m |
Max. height biomass pile | 10 m |
[/mk_table]
[mk_table style=”style3]
Pipes and Materials | |
Pipe’s Standards | 6m AISI 316L ø25×1.2mm ¾” BSP tai6m AISI 316L |
ø28×1.2mm straight ends to pressure connection | |
Weight | 1.45 kg |
Nozzles | AISI 304 or AISI 316L |
[/mk_table]
[mk_table style=”style3]
Hydraulic System | |
Planning area | 4 zones (min. 90m2 per zone) or 360m2 |
Water density (area 3m x 6m) | 3.7 mm/min |
Operating time | >90 min |
Related products | |
Valve | Model C-EL |
[/mk_table]
[/vc_column_text][/vc_colum [vc_column width=”1/4″][vc_single_image border_color=”grey” img_link_target=”_self” image=”1357″ img_size=”300 × 200″ alignment=”center” img_link_large=”yes”][vc_single_image border_color=”grey” img_link_target=”_self” image=”1360″ img_size=”300 × 201″ alignment=”center” img_link_large=”yes”][vc_single_image border_color=”grey” img_link_target=”_self” image=”1359″ img_size=”252 × 300″ alignment=”center” img_link_large=”yes”][/vc_colum [/vc_row][vc_row][vc_column width=”1/1″][/vc_colum [/vc_row]