Kentec K-Detect-iON Off-Gas Detection

Self-calibrating flammable gas and VOC sensor for early off-gas detection in BESS modules, ahead of thermal runaway.

Product information

Kentec Electronics

Certifications and approvals

  • ETL Listed to UL2075
  • CSFM Listing
  • IEC 60068-2-30
  • IEC 60068-2-6
  • IEC 61000-4-4
  • IEC 61000-4-5
  • IEC 61000-4-6
Manufacturer website

Arcofire supplies Kentec Electronics' K-Detect-iON as the early-warning layer for Battery Energy Storage System (BESS) modules and containers. Lithium-ion thermal runaway releases flammable gases and volatile organic compounds (VOCs) from the electrolyte well before a visible fire develops - K-Detect-iON is built to catch exactly this stage.

How it works K-Detect-iON is a self-calibrating flammable gas sensor that detects over 10 flammable gases, including hydrogen and methane, across a 0-100% LEL range, and is uniquely able to detect electrolyte VOCs and hydrogen in the same sensor - a combination built specifically for BESS protection. Response time to 90% of the final reading (T90) is under 30 seconds, and the sensor never needs recalibration over its working life.

Three programmable volt-free relay outputs let the sensor signal status directly, or feed an extinguishant control panel (see Kentec extinguishant release control for BESS), each with its own configurable delay and minimum run time. A tri-colour status LED and Modbus RTU communication over RS485 allow direct integration with an industrial or Modbus controller for real-time monitoring and configuration.

Placement Mounted at rack or module level - DIN rail, magnetic or wall mount - inside the battery enclosure itself, ahead of the point where smoke or heat would become detectable, and standardised across every identical module in a fleet of containers or substations.

Specification

Technical parameters

Detection method
Spectrometer
Detected gases
>10 flammable gases incl. hydrogen (H2), methane (CH4), VOC (electrolyte vapours)
Detection range
0-100% LEL
Response time (T90)
<30 seconds
Calibration
Calibration-free over service life (up to 15 years)
Relay outputs
3 programmable, volt-free changeover
Communication
Modbus RTU over RS485
Power supply
12-24V DC
Enclosure
Industrial steel, IP20
Mounting
DIN rail, magnetic or wall mountable
Operating temperature
-40°C to 75°C (H2 sensing); -40°C to 70°C (CH4 sensing)

Downloads

Datasheets and certificates