Stationary Proportioners
FireDos stationary proportioners are precision-engineered systems for accurate foam concentrate dosing in fixed industrial fire suppression installations, driven purely by the extinguishing water flow — without external power supply.
Product information
FireDos
Certifications and approvals
- FM Approved
- DNV Certified
- VdS Approved
Purely Mechanical Foam Proportioning for Industrial Fire Protection
FireDos stationary proportioners are precision-engineered systems designed for accurate foam concentrate dosing in fixed industrial fire suppression installations. Driven exclusively by the extinguishing water flow, the system operates purely mechanically — without external power supply — ensuring maximum reliability in critical emergency scenarios.
Mechanical Operating Principle
FireDos proportioners consist of a water motor directly coupled to a positive displacement dosing pump.
• Water flow drives the motor • Pump speed increases proportionally to flow rate • Foam concentrate is injected at a constant ratio • Proportioning remains stable across wide flow and pressure variations
This direct mechanical correlation guarantees consistent foam quality even during fluctuating discharge conditions or pulsating flow.
Key Advantages
• Purely mechanical operation • No electrical dependency • Constant proportioning rate • Very low pressure loss • Wide operating range • Suitable for high-viscosity foam concentrates • Compatible with AFFF, AR-AFFF and fluorine-free foams (F3) • Operating pressure up to 16 bar (static versions up to 25 bar) • ATEX versions available
Wide Flow Capacity Range
FireDos stationary proportioners are available in multiple sizes covering flow rates from approximately 300 l/min up to 25,000 l/min and beyond. Various proportioning rate configurations are available, including fixed and stepless adjustable versions depending on system design requirements.
Suitable for:
• Pump room installations • Skid-mounted foam units • Tank farm deluge systems • Monitor-based protection systems • Large industrial process areas
Environmentally Safe System Testing
FireDos systems allow full functional testing without producing premix or foam discharge.
• Foam concentrate is recirculated to the tank • Flow rate is precisely measured • No premix enters drainage systems
This ensures environmentally responsible and cost-efficient verification of system performance.
Typical Applications
• Tank farms • Chemical and petrochemical plants • Energy facilities • Aircraft hangars • Waste processing plants • Industrial production sites
FireDos Stationary Proportioners provide reliable, precise and low-maintenance foam dosing for demanding industrial fire protection systems.
Specification
Technical parameters
- Flow rate range
- ≈300 – 25,000 l/min
- Operating pressure
- up to 16 bar (static versions up to 25 bar)
- Compatible foams
- AFFF, AR-AFFF, fluorine-free (F3)
- Approvals
- FM, DNV, VdS