Valves

Alarm valves and isolation valves for sprinkler systems - wet, dry, pre-action and deluge alarm valves, OS&Y and butterfly isolation valves with tamper switches.

Product information

Certifications and approvals

  • EN 12259-2
  • EN 12259-3
  • EN 12259-4
  • EN 12259-5
  • EN 12845

Arcofire supplies the full range of valves required for automatic sprinkler installations, from the world's leading manufacturers, tested and approved to EN 12259-2 (wet alarm valves), EN 12259-3 (dry alarm valves) and EN 12259-4/5 (pre-action and deluge systems).

Alarm Valves • Wet alarm (alarm check) valve - a one-way valve that admits water into the sprinkler pipework and triggers a local and remote alarm when water flows, used on wet pipe systems • Dry pipe valve - holds back water with compressed air, for pipework in unheated areas at risk of freezing; opens when a sprinkler activates and air pressure drops • Pre-action valve - electrically supervised, requiring both a fire detection signal and sprinkler activation before water is admitted, for areas where accidental discharge must be avoided • Deluge valve - normally closed, opened by a separate detection system to discharge water through open (non-thermal) sprinklers or nozzles simultaneously across the whole system

Each alarm valve station ("trim") includes the valve body, retard chamber, pressure gauges upstream and downstream, a water motor gong or electric alarm bell, a pressure switch for remote signalling, and test and drain connections for periodic system testing as required by EN 12845.

Isolation Valves OS&Y (outside screw and yoke) gate valves and butterfly valves isolate sections of the system for maintenance. Every isolation valve controlling a sprinkler supply is fitted with a tamper (supervisory) switch, wired to the fire alarm panel, which raises a signal if the valve is not in the fully open position - a mandatory safeguard against an accidentally or maliciously closed valve leaving part of a building unprotected.

Zone control valve assemblies combine an isolation valve, non-return valve, flow switch and test/drain connection for a single floor or fire compartment, allowing each zone to be isolated and tested independently.

Specification

Technical parameters

Alarm valve types
Wet, dry, pre-action, deluge
Isolation valve types
OS&Y gate valve, butterfly valve
Supervision
Tamper (supervisory) switch on every isolation valve
Valve station trim
Gauges, water motor gong/bell, pressure switch, test/drain
Zone control assembly
Isolation valve + check valve + flow switch + test/drain
Standards
EN 12259-2, EN 12259-3, EN 12259-4, EN 12259-5